Protocols

S7 (Step7)

qianmoQqianmoQ· 更新于 2026-09-30· 阅读 101 分钟· 0 次阅读

登录后可跨设备保存划线和私人笔记登录

banner

The S7 driver talks to Siemens Simatic S7 controllers over the S7comm protocol carried on ISO-on-TCP (COTP). It exploits the advanced features of the S7-300 and S7-400 families - device status (RUN/STOP) events, system/user diagnostic events, alarms, cyclic (CYC) push subscriptions and SZL/SSL diagnostics - and provides basic PUT/GET read and write access to the S7-1200 and S7-1500 families, whose firmware does not expose the same event and diagnostics services. S7-200 and S7-200 Smart controllers are reachable too, through a small set of connection and addressing conventions documented below. The driver is also reported to work against VIPA hardware, a Siemens-compatible clone of the S7-300 with extended memory.

Most closed-source S7 stacks, and even the best-known open source one, Snap7, are built around a simple request/response pattern. PLC4X’s S7 driver goes further by giving open, non-Siemens applications access to the asynchronous, timestamped data that would otherwise require the Siemens ecosystem itself - SOFTNET OPC-DA/OPC-UA, the low-level SAPI-S7 library, or a DCS/SCADA product such as PCS7, Braumat or WinCC.

The current stable release of the driver is 0.10.0 (2022-10-04). Community support is available on the PLC4X development list (dev@plc4x.apache.org); companies offering commercial support for PLC4X drivers are listed on the project website.

Supported Operations

NameValueDescription
readC, Go and Java.
writeC, Go and Java.
subscribeGo and Java. Two independent flavors: cyclic (CYC) push of ordinary tags at a requested interval, and alarm subscriptions (ALM for a live push feed, QUERY:ALARM_S / QUERY:ALARM_8 for a one-shot fetch of what is currently buffered). Both ride the S7Comm "UserData" services that the driver probes for at connect time; a device that does not answer that probe - and S7-1200/S7-1500 controllers, which do not implement the alarm/event subsystem the S7-300/S7-400 family does - rejects a subscription with UNSUPPORTED. The C driver does not subscribe.
browseGo and Java, under the same UserData-service condition as subscribe. Enumerates the static memory areas plus the data blocks (DB) currently present on the connected device - this is a live inventory of what can be addressed, not a network scan.
discoverJava only, and only when the optional pcap4j runtime and a system libpcap are installed. Sends a PROFINET DCP broadcast and collects device announcements - this is the network-discovery API, not browse; it finds devices, it does not enumerate tags on one.

Connection String

The connection string has the layout

s7://{ip-address}?{options}

SCHEMA is always s7; cotp is the only transport and is therefore omitted. The ip address names the PLC or the CP that fronts it, and options is an ampersand-separated list of key/value parameters, documented in full below.

s7://10.10.1.33?cotp.remote-rack=0&cotp.remote-slot=3&controller-type=S7_400
When connecting to a Siemens LOGO device, add ?controller-type=LOGO to the connection string. Siemens seems to have only partially implemented the protocol on these devices: without pinning the type, the device terminates the connection as soon as the driver tries to read the SZL table it normally uses to auto-detect which S7 device family it is talking to.

Connection String Options

Name

Type

Default Value

Required

Description

Name

Siemens S7 (Basic)

Code

s7

Maven Dependency

<dependency>
  <groupId>org.apache.plc4x</groupId>
  <artifactId>plc4j-driver-s7</artifactId>
  <version>1.0.0</version>
</dependency>

Default Transport

cotp

Supported Transports

  • cotp

Config options:

pdu-size

INT

1024

Maximum size of an S7 data-packet sent to and received from the remote PLC.

max-amq-caller

INT

8

Maximum number of unconfirmed requests the PLC will accept in parallel.

max-amq-callee

INT

8

Maximum number of unconfirmed responses or requests PLC4X will accept in parallel.

controller-type

STRING

ANY

Skip controller-type detection and assume the given type.

read-timeout-ms

INT

10000

Maximum waiting time (in milliseconds) for a single S7 request/response exchange.

ha-heartbeat-interval-ms

INT

4000

S7H dual-path only: interval between heartbeat ticks (in milliseconds). Each tick pings each inner connection so a standby disruption is detected within interval + ha-failover-timeout-ms. Lower values detect faster but generate more background traffic. Default 4000 (4s).

ha-failover-timeout-ms

INT

2000

S7H dual-path only: maximum time (in milliseconds) the wrapper waits for an operation on the active inner before swapping to the alternate. The same value is used as the per-tick ping timeout in the heartbeat. Lower values fail over faster but risk swapping on transient slow responses. Default 2000 (2s).

Transport config options:

cotp

cotp.local-rack

INT

1

Rack value for the client (PLC4X device).

cotp.local-slot

INT

1

Slot value for the client (PLC4X device).

cotp.local-device-group

STRING

OTHERS

Local Device Group.

cotp.remote-rack

INT

0

Rack value for the remote main CPU (PLC).

cotp.remote-slot

INT

0

Slot value for the remote main CPU (PLC).

cotp.remote-device-group

STRING

PG_OR_PC

Remote Device Group.

cotp.local-tsap

INT

0

Local TSAP (Transport Service Access Point) identifier.

cotp.remote-tsap

INT

0

Remote TSAP (Transport Service Access Point) identifier.

cotp.tpdu-size

INT

8192

COTP PDU size for data transmission. Valid values: 128, 256, 512, 1024, 2048, 4096, 8192.

cotp.handshake-timeout-ms

INT

5000

Connection timeout for COTP handshake in milliseconds.

cotp.protocol-class

INT

0

COTP protocol class to use. Class 0 is most commonly used (simple class, no flow control).

cotp.connect-timeout-ms

INT

5000

Connection timeout in milliseconds.

cotp.read-timeout-ms

INT

0

Socket read timeout in milliseconds. 0 means no timeout.

cotp.write-timeout-ms

INT

0

Socket write timeout in milliseconds. 0 means no timeout.

cotp.no-delay

BOOLEAN

true

Enable TCP_NODELAY (disable Nagle’s algorithm).

cotp.keep-alive

BOOLEAN

false

Enable SO_KEEPALIVE.

cotp.send-buffer-size

INT

81920

Send buffer size in bytes. 0 uses system default.

cotp.receive-buffer-size

INT

81920

Receive buffer size in bytes. 0 uses system default.

cotp.local-address

STRING

Local address to bind to (optional). If not set, uses default.

cotp.local-port

INT

0

Local port to bind to (optional). 0 uses ephemeral port.

Tag Addresses

Addressing is implemented in C, Go and Java. See the protocol support matrix for what each implementation does.

General Format

The PLC4X S7 driver addresses TIA Portal’s own address notation, so addresses can generally be copied directly out of TIA Portal.

In general all S7 addresses have this format:

%{Memory-Area}{start-address}[{selection}]:{Data-Type}

If the selection is omitted, a single element is read. The selection in brackets is the shared array notation - a single index, an inclusive range, and optionally the array’s declared lower bound. See Addressing arrays for the full set of forms and what this driver can express.

Generally there are two types of addresses:

Bit-Addresses  {Memory-Area-Code}{Start-Byte-Address}.{Bit-Offset}:BOOL[{Count}]
Byte-Addresses {Memory-Area-Code}{Start-Byte-Address}:{Data-Type-Code}[{count}]

Bit addresses are only used if the datatype BOOL is used. The array notation of these can be omitted, in which case a Count of 1 is used by default. Start-Byte-Address and Bit-Offset both represent unsigned integer values.

In case of accessing data in the data block memory area, the syntax is a bit more complex:

DB{Data-Block-Number}.DB{Short-Data-Type-Code}{Start-Byte-Address}.{Bit-Offset}:BOOL[{Count}]
DB{Data-Block-Number}.DB{Short-Data-Type-Code}{Start-Byte-Address}:{Data-Type-Code}[{Count}]

When reading a STRING datatype, currently 254 characters are automatically fetched from the PLC. To limit the amount of data transferred, the STRING type declaration syntax was extended to allow declaring a shorter length:

DB{Data-Block-Number}.DB{Short-Data-Type-Code}{Start-Byte-Address}:STRING({string-length})[{Count}]

The data-block forms above carry some unnecessary boilerplate (the .DB in the middle, as well as the Short-Data-Type-Code), so a shorter syntax is also accepted, and handled identically to the long form:

DB{Data-Block-Number}:{Start-Byte-Address}.{Bit-Offset}:BOOL[{Count}]
DB{Data-Block-Number}:{Start-Byte-Address}:{Data-Type-Code}[{Count}]
DB{Data-Block-Number}:{Start-Byte-Address}:STRING({string-length})[{Count}]

Memory Areas

The S7 driver currently allows access to the following memory areas.

The Code column represents the code that is used in above general address syntax:

Not all S7 device types support the same full set of memory areas, so the last column gives more information on which types a given memory area is supported on.

CodeNameDescriptionSupported PLC Types
CCOUNTERSTODO: Document thisTODO: Document this
TTIMERSTODO: Document thisTODO: Document this
DDIRECT_PERIPHERAL_ACCESSTODO: Document thisTODO: Document this
IINPUTSInputs (Digital and Analog …​ usually Analog Inputs just have a start-address offset to separate them from the digital ones)All
QOUTPUTSOutputs (Digital and Analog …​ usually Analog Outputs just have a start-address offset to separate them from the digital ones)All
MFLAGS_MARKERSTODO: Document thisTODO: Document this
DBDATA_BLOCKSMemory areas containing user-defined data structures usually accessed by the integer data block number. Please note that data block addresses have a little more complex address format.All
DBIINSTANCE_DATA_BLOCKSTODO: Document thisTODO: Document this
LDLOCAL_DATATODO: Document thisTODO: Document this

Data Types

CodeShort-CodeNameDescriptionSize in bitsSupported PLC Types
Bit-Strings (Will all interpreted as sequence of boolean values in PLC4X)
BOOLXBitSingle boolean value1All
BYTEBByteArray of 8 boolean values1All
WORDWWordArray of 16 boolean values2All
DWORDDDouble-WordArray of 32 boolean values4All
LWORDXLong-WordArray of 64 boolean values8S7_1500
Integer values
SINTBSmall int8 bit integer (signed)1S7_1200, S7_1500
USINTBSmall unsigned int8 bit integer (unsigned)1S7_1200, S7_1500
INTWInteger16 bit integer (signed)2All
UINTWUnsigned integer16 bit integer (unsigned)2S7_1200, S7_1500
DINTDDouble integer32 bit integer (signed)4All
UDINTDUnsigned Double Integer32 bit integer (unsigned)4S7_1200, S7_1500
LINTXLong integer64 bit integer (signed)8S7_1500
ULINTXUnsigned long integer64 bit integer (unsigned)8S7_1500
Floating point values
REALDReal32 bit IEEE 754 full precision floating point value (signed)4All
LREALXLong Real64 bit IEEE 754 double precision floating point value (signed)8S7_1200, S7_1500
Character values
CHARBCharacter8 bit character1All
WCHARXDouble byte character16 bit character value2S7_1200, S7_1500
STRINGXStringString 2 + n bytes1All
WSTRINGXDouble byte StringString of 16 bit characters 2 + n bytes1S7_1200, S7_1500
Temporal values
S5TIMEXS5 TimeS5 Time (like in duration)2S7_300, S7_400, S7_1500
TIMEXTimeTime (like in duration) (Minutes, Seconds, Milliseconds)4All
LTIMEXLong TimeLong Time (like in duration) (Minutes, Seconds, Milliseconds, Microseconds, Nanoseconds)8S7_1500
DATEXDateDate2All
TIME_OF_DAYXTime of dayTime (like in 4:40PM)4All
DATE_AND_TIMEXDate and TimeDate and time (like in 03.05.2020 4:40 PM)8S7_300, S7_400, S7_1500

Examples

AddressMeaning
%DB1.DBX0.0:BOOLthe single bit at data block 1, byte 0, bit 0
%DB10.DBW20:INTa 16-bit signed integer at data block 10, byte 20
%I0.0:BOOLthe single bit at input byte 0, bit 0
%MD100:DINTa 32-bit signed integer at flag/marker byte 100
%DB1.DBB0[0..9]:BYTE10 bytes starting at data block 1, byte 0, returned as a list
%DB5:10:INTa 16-bit signed integer at data block 5, byte 10, using the shorter data-block syntax
%DB1.DBB0[0..15]:RAW_BYTE_ARRAY16 raw bytes starting at data block 1, byte 0, decoded as BYTE - RAW_BYTE_ARRAY is accepted as an alias for BYTE
%DB1.DB0:STRING(80)an STRING of up to 80 characters at data block 1, byte 0 - fewer than the 254-character default
%DB1.DB0:STRINGa STRING at data block 1, byte 0, read at its default maximum length
ALMsubscribes to the live alarm push feed (see Protocol Details)
QUERY:ALARM_Sone-shot read of the alarms currently buffered on the PLC, ALARM_S layout

Table 1. Examples

Notes and Tips

Especially when it comes to the input- and output addresses for analog channels, the start addresses are configurable and hereby don’t always start at the same address. In order to find out what addresses these ports have, please go to the device setting of your PLC in TIA Portal.

devsettings

Especially pay attention to this part:

iosettings

In above image you can see that this device has 8 digital inputs (DI 8) and 2 analog inputs (AI 2_1) as well as 6 digital outputs (DQ 6).

The start addresses of the digital inputs and outputs start directly at 0. The analog inputs however start at address 64.

Each digital input and output can be addressed by a single bit-address (start-address and offset) or can be read in a block by reading a full byte starting at the given start address without providing a bit offset.

Protocol Details

Siemens S7-200 / S7-200 Smart

The S7-200 and the newer S7-200 Smart are lower-end controllers that behave a little differently from the S7-300/400/1200/1500 family. They can still be reached with the S7 driver over Ethernet (ISO-on-TCP), but they need a couple of specific connection settings and use a different convention for addressing their variable memory.

This section collects what the community has found to work (see PLC4X issues devlive-community/knowforge#1925 and devlive-community/knowforge#2641).

Connecting

Two things are important when connecting to an S7-200 (Smart):

  1. Disable the automatic controller-type detection by passing controller-type=S7_200. The S7-200 does not answer the SZL/SSL identification request the driver normally uses to auto-detect the CPU family, so — as with the LOGO device mentioned above — the type has to be provided explicitly.
  2. Provide the TSAP (Transport Service Access Point) values explicitly. The S7-200 (Smart) expects both the local and the remote TSAP to be 0x0200, which is 512 in decimal. Set them with cotp.local-tsap=512 and cotp.remote-tsap=512; a non-zero TSAP overrides the rack/slot based addressing.

A minimal, working connection string therefore looks like this:

s7://192.168.12.100?cotp.local-tsap=512&cotp.remote-tsap=512&controller-type=S7_200

cotp.remote-rack=0 and cotp.remote-slot=0 are the defaults, so they are optional, but may be added for clarity:

s7://192.168.12.100?cotp.remote-rack=0&cotp.remote-slot=0&cotp.local-tsap=512&cotp.remote-tsap=512&controller-type=S7_200

Both reading and writing have been confirmed to work against an S7-200 Smart with this configuration.

Addressing the V (variable) memory area

The S7-200 keeps its user variables in a V (variable) memory area, addressed in the Siemens tooling (STEP 7-Micro/WIN) as, for example, VW310, VD732 or V350.0. The S7 driver does not have a dedicated V memory-area code.

On the S7-200, however, the V area is simply an alias for Data Block 1 (DB1). Any V address can therefore be read and written by addressing DB1 instead, using the normal data-block syntax described above:

S7-200 notationPLC4X addressMeaning
VB100%DB1.DBB100:BYTEsingle byte at V100
VW310%DB1.DBW310:INT16-bit word at V310
VD732%DB1.DBD732:UDINT32-bit double word at V732
V350.0%DB1.DBX350.0:BOOLsingle bit V350.0

The shorter data-block notation works as well, for example %DB1:732:UDINT for VD732.

The M (flags/markers) memory area is addressed as usual, for example %M10.0:BOOL or %MW20:INT.

NoteNative support for a dedicated V memory-area code may be added in a future release. Until then, please use the DB1 alias shown above.

Actors participating in the communication process

PLC programming in general is a Pandora’s box!

Here we will assume that you use standard technological functions/libraries within your development cycle, therefore, at this point it is important to point out the actors that participate in this dialogue between the driver and the PLC and how they affect the communication cycle.

The different actors involved in communication are shown in image 1.

  1. PLC (AS), the controller. AS is the reference used in PCS7.
  2. App, your application.
  3. PLC4X, implementation of the S7 driver.
  4. OS, PLC operating system.
  5. PCS7, represents the technological functions used in the PLC. PCS7 are Siemens DCS libraries.
  6. S7App, your application that runs on the PLC.
  7. CP, the communications CP will depend on your architecture and requirements, for an S7-300 it will be a CP 343-1 or a CP 443-1 for an S7-400.

S7 Read/Write

S7 Event Subscription

NoteonSubscribe accepts exactly two kinds of tag: an S7AlarmTag (ALM, QUERY:ALARM_S or QUERY:ALARM_8) subscribed as an EVENT, or an ordinary S7Tag subscribed as CYCLIC; anything else is rejected with INVALID_ADDRESS. The MODE, SYS and USR subscriptions this section once documented were built on an addEventField() / S7ModeEvent / S7SysEvent / S7UserEvent API that is no longer present in the source tree; those subsections have been commented out in this page’s source rather than deleted. ALM and cyclic (CYC) subscriptions are what actually works today.

The S7 driver allows the subscription to asynchronous events generated in the PLC.

This type of event is generated by S7-300, S7-400, G120C-PN, S120-PN controllers and VIPA devices. Unfortunately for the S7-1200 and S7-1500 series this functionality has been superseded.

NoteFor a complete list of compatibility between the S7-300,400 and S7-1200 & S7-1500, you can see the document in [1] provided by Siemens.

These services have the following advantages:

  1. Report the status of the CPUs and other components within the control architecture that support it (CP, IM, DI, etc).
  2. Transfer of values when a change occurs.
  3. Associate values to the events sent.
  4. A better handling of the TimeStamp of the associated values.

The messages are classified into two groups depending on how they are generated:

  1. SCAN: All those events generated by the system or preset in Step7 (TIA Portal). The change of state of the configured signals is carried out by the operating system at specific intervals (500 ms, 100ms or 16 ms).
  2. ALARM: These are events generated by the user application using the alarm blocks (ALARM_S, ALARM_SQ, NOTIFY, ALARM, ALARM_8). In addition to user applications, these events can be generated from technological functions such as PCS7 or Braumat.

The data associated with the events is represented in a HashMap in order to facilitate its transfer to other applications based on a standard such as JMS, MQTT or other messaging technology.

The handling of the TimeStamp of the SCAN type events is generated in the computer. In ALARM type messages the TimeStamps are generated in the PLC. It is extremely important that the date and time synchronization is done between both computers and PLC.

The values associated with the events can have different types of representation, so their interpretation must be agreed upon during the programming of the application in the PLC and your application.

For each type of event, the particular fields of type <String, T> will be arranged within the Map. These will be documented for each type of event.

To maximize the use of the data fields associated with the events, the use of the intra-area pointer system and the ANY type pointer is recommended in the PLC, As well as the recommendations for the management of the time stamp [2].

At the user application level App, you can use the PLC4X API to subscribe SCAN or ALARM type events by selecting any of the following fields according to the requirement:

  1. MODE: Change of operating state in the controller, change from STOP to RUN and vice versa.
  2. SYS: System events, associated with internal events of the controller or events previously parameterized for their indication.
  3. USR: Events programmed by the user and that are registered in the internal diagnostic buffer.
  4. ALM: Alarm events generated by the user program, ALARM_S, ALARM_8, NOTIFY.

In the following sections we will describe in more detail the functionalities of each field.

SCAN Events

NoteThe MODE, SYS and USR subscriptions that this section used to describe are not available in the current driver: the S7ModeEvent, S7SysEvent, S7UserEvent and addEventField() API they were written against no longer exists in the source tree. Those subsections are retained in this page’s source as a comment block rather than deleted, so the protocol-level description can be restored if the API returns or rewritten against the current one. What the driver implements today is the ALM subscription described below, and cyclic (CYC) subscriptions covered further on.

ALARM Events

Subscription to ALM type events
NoteThis is the one event class of the four originally described in this section that the current driver actually implements, as a real PlcSubscriptionRequest on an S7AlarmTag (ALM for the live push feed shown here; QUERY:ALARM_S / QUERY:ALARM_8 for a one-shot fetch of what is currently buffered - see S7CotpConnection.onSubscribe). The diagram below illustrates the message flow at the protocol level. Note that the older S7AlarmEvent class is not part of the current API - a subscription delivers a standard PlcSubscriptionEvent.

The registration sequence for subscription is the typical one carried out so far (01)(02)(03)(04)(05). From that moment on, you can start receiving alarm events asynchronously.

Depending on your application, you can make a request for the currently active alarms in the alarm buffer of the PLC(AS), in this way you can prepare a reception buffer or establish the correct state of a state machine that depends on the Active events in the controller.

You must take into account that when making the request (06), from a few to hundreds of alarms can be stored depending on the complexity of your application and the capacity of the PLC (AS).

In this scenario, the PLC4X driver maintains the dialogue with the OS to receive sequentially (07)(08)(09)(10)(11)(12)(13)(14) the alarms stored on the controller, to later transfer them to the user application App (15).

At the end of the subscription process, it will begin to receive the events generated by the system, such as high precision time signals (16)(17)(18)(19) or events generated by the user application (20)(21)(22).

This simple sequence of events is used by process applications based on PCS7, for the handling of alarms, events and logging of practically all the events of the distributed control system (DCS).

Another important feature of the driver is the ability to recognize the alarms generated from the PLC(AS). In (23)(24)(25) the S7App application generates an alarm/event that is required to be acknowledged by the user to continue with the execution of a specific routine. The user applications App generates the acknowledgment (27)(28) using the corresponding alarm identifier, the OS is responsible for making the confirmation (29)(30) and asynchronously generating an event for the update of the state machine in the App(31)(32).

Within the cyclical execution of the application S7App waits for the confirmation of the alarm (26) to continue with some specific routine.

TODO: Field description

FieldTypeDescription
TYPE
TIMESTAMP
TIMESTAMP_GOING
TIMESTAMP_COMING
ASSOCIATED_VALUES
MAP
EVENT_ID
EVENT_STATE
STATE
ACKSTATE_GOING
ACKSTATE_COMING
EVENT_GOING
EVENT_COMING
EVENT_LAST_CHANGE
SIG
SIG_[1…​8]
SIG_STATE
SIG_[1…​8]_STATE
SIG_DATA
SIG_[1…​8]_DATA
SIG_[1…​8]_DATA_GOING
SIG_[1…​8]_DATA_CO
SIG_[1..8]_DATA_STATUS
SIG_[1…​8]_DATA_SIZE
SIG_[1…​8]_DATA_LENGTH

TODO: Example code

Cyclic subscription (CYC)

The cyclical subscription allows the acquisition of data in passive mode, that is, the data is sent from the PLC in a cyclical and synchronous way. Unlike the MODE/SYS/USR event classes above, this one is implemented by the current driver: subscribe an ordinary S7Tag with subscription type CYCLIC and a requested Duration, and the driver picks a matching hardware time base and factor for you.

The data transfer has three time bases:

  1. B01SEC: Time base 0.1 Sec. (100 mSec.).
  2. B1SEC: Time base 1.0 Sec.
  3. B10SEC: Time base 10 Sec.

The driver prefers the coarsest base whose factor still fits in a byte, because S7-300 firmware from V3.2 onward rejects B01SEC (100 ms) subscription requests outright (errCode=0xD804), honoring only B1SEC and B10SEC; sub-second requests still fall back to B01SEC since it is the only base able to express them, and will be rejected by that firmware.

SZL System Status List

The system status list gives access to the operating data of the PLC, such as memory space, operating status, status of the control switches, as well as diagnostic data of expansion cards or decentralized peripherals, PROFIBUS or PROFINET .

This is fundamental data to determine the quality of the data supplied by the PLC.

By initiating the connection with the PLC you can determine its operating status, which will allow you to define the quality of the data taken and what the implemented application can do or not, eventually this is the procedure carried out by the Siemens CPs.

NoteWhy SZL and not SSL? Well, creative freedom. The translation of the manuals from German to Spanish use SZL and German to English use SSL. Both the source code and the documentation use this reduction to keep the text uniform.

Due to the fact that the data structures are so varied, basically one per type of diagnosis, the decision was made to return these as an array of bytes, leaving the developer to implement the parser according to their requirements.

For a first approach to using system state lists a byte array to JSON notation parser is available at "org.apache.plc4x.java.s7.readwrite.utils.StaticHelper.SZL" .

NoteMake use of the XXX document for a detailed explanation of each SZL, since as indicated, everything will depend on the hardware you have installed.
NoteThe driver itself reads SZLs internally - to auto-detect the controller type at connect time, and to back browse - through S7SzlService/S7CotpConnection, not through a user-addressable PlcTag. The SZL_ID=…​;INDEX=…​ tag address used in the walkthrough below does not match any pattern S7PlcTagHandler accepts today (it does not start with the % every other S7 address requires), so addTagAddress with that string throws PlcInvalidTagException against the current driver. The SZL_ID/INDEX encoding itself and the JSON shape of a response remain accurate and are kept for reference; only the specific "read it as a normal PlcTag" mechanism shown here is out of date.

Notation for SZL request

The access to the SZL of the PLC is done as a read request, where the PLCTag is formed by two fields "SZL_ID" and "INDEX".

  1. SZL_ID: Number assigned to the SZL list. There are variants of the SZL_ID depending on whether the request is total, partial or just the header. To facilitate its use, the representation will always be in hexadecimal with the format 0xxyID.
  +--+--+--+--+--+--+--+--+--+--+--+--+--+--+--+
  |15|14|13|12|11|10| 9| 8| 7| 6| 5| 4| 3| 2| 1|
  +--+--+--+--+--+--+--+--+--+--+--+--+--+--+--+
  \__________/\__________/\____________________/
   Module      Number of   Number of the partial
   class       the partial list
               list
               extract
  1. Number of the partial list : The number of the partial SZL list you want to read.
  2. Number of the partial list extract: Defines which part of the partial list you want to extract. It varies from list to list.
  3. Module Class: The requests for the partial list depend on the hardware that is being used, generally the IM (communication cards), FM (special functions) and CP (periphery controller) have their own diagnostic system, which can be consulted through of the SZL_ID/INDEX PlcTag.
  Module Class:
  +--------------+-----------------+
  | Module class | Coding (Binary) |
  +--------------|-----------------+
  |     CPU      |      0000       |
  +--------------|-----------------+
  |     IM       |      0100       |
  +--------------|-----------------+
  |     FM       |      1000       |
  +--------------|-----------------+
  |     CP       |      1100       |
  +--------------|-----------------+
  1. INDEX: Number of the required sublist. To facilitate its use, the representation will always be in hexadecimal with the format 0xhhhh.

mi_001

public static void main(String[] args) throws Exception {
    System.setProperty(SimpleLogger.DEFAULT_LOG_LEVEL_KEY, "trace");

    System.out.println("******************************************************************************************");
    System.out.println("Before using, take a look at:");
    System.out.println("System Software for S7-300/400.\r\nSystem and Standard Functions - Volume 1/2");
    System.out.println("Document: A5E02789976-01");
    System.out.println("Chapter 34 System Status Lists (SSL).");
    System.out.println("URL: https://cache.industry.siemens.com/dl/files/604/44240604/att_67003/v1/s7sfc_en-EN.pdf");
    System.out.println("******************************************************************************************");

    try (PlcConnection connection  new DefaultPlcDriverManager().getConnection("s7://10.10.1.33?cotp.remote-rack=0&cotp.remote-slot=3&controller-type=S7_400")) { //(01)

        final PlcReadRequest.Builder readrequest  connection.readRequestBuilder(); //(02)

        readrequest.addTagAddress("MySZL", "SZL_ID=16#0012;INDEX=16#0000"); //(03)

        final PlcReadRequest rr  readrequest.build(); //(04)
        final PlcReadResponse szlresponse  rr.execute().get(); //(05)

        if (szlresponse.getResponseCode("MySZL") = PlcResponseCode.OK){ //(06)

            Collection<Byte>  data  szlresponse.getAllBytes("MySZL"); //(07)
            byte[] dbytes  ArrayUtils.toPrimitive(data.toArray(new Byte[data.size()])); //(08)

            SZL szl  SZL.valueOf(0x0012); //(09)
            ByteBuf wb  wrappedBuffer(dbytes); //(10)
            StringBuilder sb =  szl.execute(wb); //(11)
            System.out.println(sb.toString());  //(12)

        } else if (szlresponse.getResponseCode("MySZL") = PlcResponseCode.NOT_FOUND){ //(13)
                System.out.println("SZL is not supported.");
        }

            Thread.sleep(2000);
            System.out.println("Bye...");

      }
    }

The request for the SZL lists follows the same pattern of variable readings, for each request a response, unlike the request for process variables where several can be grouped in a single request, the SZL request must correspond to one request to one petition.

Like other requests, the connection URL (01) is established and the request constructor instance (02) is created. The associated PLCTag is added to the diagnostic list (one per request), in this case the SZL_ID=0x0012 and INDEX=0x0000 (03) which allows obtaining the identification and firmware of the PLC.

In (04) and (05), we prepare and execute the request to the PLC. If we have a valid response (06) we can perform the processing of the data stream obtained, which as indicated is an array of bytes which is obtained in (07) and (08).

As we pointed out in the support libraries, we have an "SZL" object (an enum), which allows us to select the appropriate parser based on the numerical index SLZ_ID (09). In (10) we make a wrapper in a ByteBuf type (from the Netty library) in order to pass it to the "szl" instance through the "execute" method (11).

When processing the data buffer we must obtain in (12) a StringBuilder with the JSON representation.

{"RECORDS":[{"AUSBG2":0,"AUSBG1":61,"BGTYP":130,"INDEX":1,"MIFB":"6ES7 417-4XT05-0AB0 "},{"AUSBG2":0,"AUSBG1":2,"BGTYP":130,"INDEX":6,"MIFB":"6ES7 417-4XT05-0AB0 "},{"AUSBG2":768,"AUSBG1":22021,"BGTYP":0,"INDEX":7,"MIFB":"                    "},{"AUSBG2":3,"AUSBG1":22021,"BGTYP":0,"INDEX":129,"MIFB":"Boot Loader         "}],"LENGTHDR":28,"SZL-ID":17,"INDEX":0,"N_DR":4}

As noted above, the parser performed on the SZL enum is not complete, so the missing information must be obtained from the returned fields. For further details you should consult [].

In case of not being able to process the request, it is detected in (13) to take the necessary measures.

The following diagram represents the information in JSON format.

From the obtained StringBuilder, you can use the JSON processor of your choice to access the different fields.

Module classSZL-IDImplemented
SZL List16#xy00Tested with S7-400, JSON
Module identification16#xy11Tested with S7-400, JSON
CPU characteristics16#xy12Tested with S7-400, JSON
User memory areas16#xy13Tested with S7-400, JSON
System areas16#xy14Tested with S7-400, JSON
Block types16#xy15Tested with S7-400, JSON
Interrupt status16#xy22Tested with S7-400, JSON
Assignment between process image partitions and OBs16#xy25Tested with S7-400, JSON
Communication status data16#xy32Tested with S7-400, JSON
H CPU group information16#xy71
Status of the module LEDs16#xy74Tested with S7-400, JSON
Switched DP slaves in the H-system16#xy75
Module status information16#xy91Tested with S7-400, JSON
Rack / station status information16#xy92Tested with S7-400, JSON
Rack / station status information16#xy94Tested with S7-400, JSON
Extended DP master system / PROFINET IO system information16#xy95Tested with S7-400, JSON
Module status information, PROFINET IO and PROFIBUS DP16#xy96Tested with S7-400, JSON
Tool changer information (PROFINET IO)16#xy9CTested with S7-400, JSON
Diagnostic buffer of the CPU16#xyA0Tested with S7-400, JSON
Module diagnostic information (data record 0)16#xyB1Tested with S7-400, JSON
Module diagnostic information (data record 1), geographical address16#xyB2Tested with S7-400, JSON
Module diagnostic information (data record 1), local address16#xyB3Tested with S7-400, JSON
Diagnostic data of a DP slave16#xyB4Tested with S7-400, JSON

More Information

  1. https://snap7.sourceforge.net/
  2. https://support.industry.siemens.com/cs/document/13649203/simatic-net-pc-software-s7-programming-interface?dti=0&dl=en&lc=es-ES
  3. https://support.industry.siemens.com/cs/document/109797648/simatic-comparison-list-for-s7-300-s7-400-s7-1200-s7-1500?dti=0&lc=en-WW
  4. https://support.industry.siemens.com/cs/mdm/109746537?c=98956468747&lc=es-DO
  5. https://support.industry.siemens.com/cs/document/15166942/writing-user-specific-information-to-the-diagnostic-buffer-of-a-cpu-(sfc-52)?dti=0&lc=en-ES
  6. https://support.industry.siemens.com/cs/document/24013249/how-do-you-display-alarm_s-or-alarm_d-messages-with-process-values-(so-called-associated-values)-on-a-wincc-flexible-operator-panel-?dti=0&lc=en-WW
  7. https://support.industry.siemens.com/cs/document/109481157/comunicaci%C3%B3n-entre-paneles-de-operador-simatic-hmi-y-convertidores-de-frecuencia-sinamics-g120-para-el-manejo-y-la-visualizaci%C3%B3n-de-avisos-de-fallo-y-de-advertencia-(enlace-directo-sin-controlador)?dti=0&lc=es-WW
  8. https://support.industry.siemens.com/cs/document/97550333/sinamics-g-s-hmi-direct-access?dti=0&lc=en-WW
  9. https://support.industry.siemens.com/cs/document/21402122/technology-cpus-technology-template-error-messages-?dti=0&lc=en-WW
  10. https://support.industry.siemens.com/cs/document/77467239/transforming-warning-and-error-messages-of-a-sinamics-drive-with-the-aid-of-the-xml-parser-and-integrating-them-into-a-step-7-hmi-project?dti=0&lc=en-WW
  11. https://support.industry.siemens.com/cs/document/24037531/%C2%BFqu%C3%A9-pasos-de-configuraci%C3%B3n-hay-que-realizar-en-el-simotion-scout-y-el-wincc-flexible-para-que-se-muestren-los-avisos-alarm_s-y-las-alarmas-tecnol%C3%B3gicas-dentro-del-wincc-flexible-runtime-?dti=0&lc=es-ES